Transformer Standard current transformer are also called precision current transformers, current transformer standards, standard CT and current transformer standards. Transformer standards are divided into current transformer standards and voltage transformer standards. Standard current transformers are used in the error test of transformers. Used as a current transformer calibration standard
technical parameter
1. Temperature:
2. Relative humidity
3. Rated Primary Current:5-5000A 5A,1A
4.Rated secondary current:5 1A
5 Accuracy Class 0.05S
6. Allow long-term work under the rated current; More than120A across the core.
Precautions:
1. The current of standard CT and tested CT must be the same in CT calibration.
2. Follow the given wiring diagram strictly.
3. Test whether the load box is accurate or not before calibrating the transformer.
4. Forbid secondary winding opening during the calibration.
5. Select demagnetization before calibration.The wiring diagram is shown in figure 5.
Short out the secondary winding before cutting off the power when the demagnetization is finished.
6.Principle wiring diagram of CT with large current generator is similar to above diagram. They are the same except the output winding of large current generator and primary winding of transformer are the same one.
Transformers,Distribution and Power Transformer,Varivolt
Safety Transformers
Diesel Generators
Industrial Panels
Stabilizers
Energy Saver
Industrial Panels
Transformer Standard current transformer are also called precision current transformers, current transformer standards, standard CT and current transformer standards. Transformer standards are divided into current transformer standards and voltage transformer standards. Standard current transformers are used in the error test of transformers. Used as a current transformer calibration standard
technical parameter
Temperature -5 40
Relative humidity 80%
Rated Primary Current 5-5000A 5A,1A
Rated secondary current 5A 1A
Accuracy Class 0.05S
Allow long-term work under the rated current; More than120A across the core.
Precautions
The current of standard CT and tested CT must be the same in CT calibration.
Follow the given wiring diagram strictly.
Test whether the load box is accurate or not before calibrating the transformer.
Forbid secondary winding opening during the calibration.
Select demagnetization before calibration.The wiring diagram is shown in figure 5.
Short out the secondary winding before cutting off the power when the demagnetization is finished.
Principle wiring diagram of CT with large current generator is similar to above diagram. They are the same except the output winding of large current generator and primary winding of transformer are the same one.
Rated Input Current:5A
Rated Output Current:2.5mA
Turns ratio:2000:1
Phase Angle Error:less than 20'(1A,100)
Linear Range:0~20A(100)
Mounting(mm):D5.0
* Small size
* High accuracy
* Good consistency
* Used for current and power measurement
ABO Series (8 frames) perfect designed plastic case current transformer, advanced snap on body, high accuracy (up to Class 0.2S),
humanization transparent cover and lead seal hole design makes the CT very easy to indentify after long term use and perfect
anti-stealing electricity.
Features
1:Safe, easy to install, portable
2:Wide inner window, allowing clamping of big cables or bus-bars
3:Wide range of sizes to accommodate all the existing installations
Applications:
1:Current measurement, monitoring and protection for electrical wiring and equipment.
2:Current and power measurement for electric motors, lighting, air compressor, heating and ventilation system, air-condition equipment and automation - control system.
3:Current, power and energy monitoring device.
4:Relay protection device.
MBO Series (9 frames) perfect designed plastic case current transformer, advanced snap on body, high accuracy (up to Class 0.2S),
humanization transparent cover and lead seal hole design makes the CT very easy to indentify after long term use and perfect
anti-stealing electricity.
Features
1:Safe, easy to install, portable
2:Wide inner window, allowing clamping of big cables or bus-bars
3:Wide range of sizes to accommodate all the existing installations
Applications:
1:Current measurement, monitoring and protection for electrical wiring and equipment.
2:Current and power measurement for electric motors, lighting, air compressor, heating and ventilation system, air-condition equipment and automation - control system.
3:Current, power and energy monitoring device.
4:Relay protection device.
The MES series of current transformer are convenient for mounting in many ways.The most current transformer need the special mounting and the MES series used the mounting of DIN typing without a lot of times.The protective cover for terminal block used the switching device with safety and quick.
Feature:
1:Three built in fixing methods: Panel/Din Rail/Busbar
2:Built in hinged terminal cover
3:Compact design
4:Primary current up to 3000A
Applications:
1:Current measurement, monitoring and protection for electrical wiring and equipment.
2:Current and power measurement for electric motors, lighting, air compressor, heating and ventilation system, air-condition equipment and automation - control system.
3:Current, power and energy monitoring device.
4:Relay protection device.
CP range of current transformers are compact-smaller than other models with the current ratio of the transformer
is small.Clamshell-style terminal cover is well protected by the second terminal.
With related accessories you can use Din rail mounting a current from 5A to 3000A.
Features:
Three built in fixing methods: Panel/Din Rail/Busbar
Built in hinged terminal cover
Compact design
Primary current from 5A to 3000A
Applications:
Current measurement, monitoring and protection for electrical wiring and equipment.
Current and power measurement for electric motors, lighting, air compressor, heating and ventilation system,
air-condition equipment and automation-control system.
Current, power and energy monitoring device.
Relay protection device.