AC Input Microwave Motion Sensor - Highbay Version
AC Input Microwave Motion Sensors
Microwave Motion Sensors AC Input
HNS203HB
5.8GHz C-band microwave motion sensor, tri-level dimming control.
Operating voltage: 120~277V AC, 50/60Hz.
Rated load: 400W @ 120VAC, (capacitive)
Features
5.8GHz C-band microwave motion sensor, tri-level dimming control.
Operating voltage: 120~277V AC, 50/60Hz.
Rated load: 400W @ 120VAC, (capacitive)
800W @ 200~277VAC, (capacitive)
Stand-by power: ?1w.
Dual-PD technology, real Da ylight mo nitoring function for built-in application.
Zero-cross point operation, protect the sensor relay against the in-rush current, secure the max. load and life time of the relay .
Detection range up to 18m in diameter.
Mounting height: 10~12m.
Operation temperature:-20+70
RoHS compliant.
IP rating: IP20.
Setting
Detection range
Detection range can be reduced by selecting the combination on the DIP switches to fit precisely each application.
Hold-time
Hold-time means the time period to keep the lamp on 100% after motion detected.
*when hold-time set as 3s, sensor enters into test mode, this test mode is mainly for users to choose the desired detection range.
In this mode, the daylight sensor is disabled, when there is no motion, fixture keeps off, when there is motion detected, fixture keeps a cycle of 3s on and 2s off.
Daylight sensor
Daylight sensor means the daylight threshold to enable or disable the sensor function.
"Disable": The sensor works always, even during daylight.
"50lux": The sensor works only in twilight.
"10lux, 2lux": The sensor works only in the dark.
Stand-by period
This is the time period that the lamp remains at a low light level before it is completely switched off in the long absence of people.
"+" : means bi-level dimming control, the fixture never switch off.
Stand-by dimming level
This is the dimmed low light level you would like to have after the hold-time in the absence of people.
*0% means on/off control.
10%--Vdim=1.5Vdc 30%--Vdim=3.0Vdc50%--Vdim=5.0Vdc
AC Input Microwave Motion Sensor - Highbay Version
AC Input Microwave Motion Sensors
Microwave Motion Sensors AC Input
HNS203HB
5.8GHz C-band microwave motion sensor, tri-level dimming control.
Operating voltage: 120~277V AC, 50/60Hz.
Rated load: 400W @ 120VAC, (capacitive)
Features
5.8GHz C-band microwave motion sensor, tri-level dimming control.
Operating voltage: 120~277V AC, 50/60Hz.
Rated load: 400W @ 120VAC, (capacitive)
800W @ 200~277VAC, (capacitive)
Stand-by power: 1w.
Dual-PD technology, real Daylight monitoring function for built-in application.
Zero-cross point operation, protect the sensor relay against the in-rush current, secure the max. load and life time of the relay .
Detection range up to 18m in diameter.
Mounting height: 10~12m.
Operation temperature:-20??+70??
RoHS compliant.
IP rating: IP20.
Setting
Detection range
Detection range can be reduced by selecting the combination on the DIP switches to fit precisely each application.
Hold-time
Hold-time means the time period to keep the lamp on 100% after motion detected.
*when hold-time set as 3s, sensor enters into test mode, this test mode is mainly for users to choose the desired detection range.
In this mode, the daylight sensor is disabled, when there is no motion, fixture keeps off, when there is motion detected, fixture keeps a cycle of 3s on and 2s off.
Daylight sensor
Daylight sensor means the daylight threshold to enable or disable the sensor function.
"Disable": The sensor works always, even during daylight.
"50lux": The sensor works only in twilight.
"10lux, 2lux": The sensor works only in the dark.
Stand-by period
This is the time period that the lamp remains at a low light level before it is completely switched off in the long absence of people.
"+" : means bi-level dimming control, the fixture never switch off.
Stand-by dimming level
This is the dimmed low light level you would like to have after the hold-time in the absence of people.
*0% means on/off control.
10%--Vdim=1.5Vdc 30%--Vdim=3.0Vdc50%--Vdim=5.0Vdc
5V/12V DC Input Microwave Motion Sensor - Standard Version
DC Input Motion Sensor Module
Adjustable Motion Sensor Module
HNS101
5.8GHz C-band microwave.
Input voltage 12V DC (5V & 24V DC version available on request).
Input current:25mA.
5V DC high-low voltage output signal.
Features
5.8GHz C-band microwave.
Input voltage 12V DC (5V & 24V DC version available on request).
Input current:�?�25mA.
5V DC high-low voltage output signal.
Super compact, flexible to be integrated into any suitable fixtures.
Dual-PD technology, real Lux-Off function for built-in application.
8 pin DIP switch setting, multiple options to meet different customer demands. Detection range up to 12m in diameter.
Mounting height: 3~6m.
Operation temperature: -20�?? ~ +70�??.
RoHS compliant.
Settings
Detection range
Detection range can be reduced by selecting the combination on the DIP switches to fit precisely each application.
Hold-time
Hold-time means the time period to keep the lamp on 100% after motion detected.
*when hold-time set as 3s, sensor enters into test mode, this test mode is mainly for users to choose the desired detection range. In this mode, the daylight sensor is disabled, when there is no motion, fixture keeps off, when there is motion detected, fixture keeps a cycle of 3s on and 2s off.
Daylight sensor
Daylight sensor means the daylight threshold to enable or disable the sensor function.
"Disable":The sensor works always, even during daylight. w50lux, 25lux": The sensor works only in twilight.
"10lux, 2lux": The sensor works only in the dark.
5V/12V DC Input Microwave Motion Sensor Highbay Version
DC Input Motion Sensor Module
Highbay DC Input Motion Sensor
HNS111HB
5.8GHz C-band microwave.
Input voltage 12V DC (5V & 24V DC version available on request).
Features
5.8GHz C-band microwave.
Input voltage 12V DC (5V & 24V DC version available on request).
0~10V DC output signal
Super compact, flexible to be integrated into any suitable fixtures.
Dual ï¹£ PD technolo gy, real Daylight monitoring function for built-in application.
IR remote commissioning, easy setting and user friendly.
Detection range up to 18m in diameter.
Mounting height: 10~1 2m.
Operation temperatur e: -2 ~ +70
RoHS compliant.
Settings(Remote control IR12)
Permanent ON/OFF function
Press ON/OFF button, fixture goes to permanent on or permanent off mode, sensor is disabled.
*press "Auto" ,"Reset" or "Ambient learn" to quit this mode.
Dim +/-
Press "Dim" button to automatically dim up or down the light brightness during hold-time from 10% to 100%. Another press to lock it down when desired brightness is achieved.
*after desired brightness is locked down, if user wants to dim again reversely, just press the Dim button again and then lock down the new brightness again.
Sensor mode
Press "Auto" button, the sensor starts to work and all settings remain the same as the latest status before the light was switched on/off.
Reset function
Press "Reset" button, all settings go back to factory default settings.
Factory default settings
Sensitivity=100%
Daylight sensor=disable
Hold time=90s
Twilight time=5min
Twilight level=10%
Ambient learn
Press "Ambient learn" button, the latest surrounding lux value overwrites previous lux value learned, and set as the daylight threshold. This feature enables the fixture to function well in any real application circumstance.
Test mode
"Test mode" is for testing purpose only, for users to check the functionality and choose the desired detection range. The sensor goes to test mode automatically after pressing this button.
Users can quit this mode by pressing "ON/OFF", "Reset' or any button of "Hold time". The sensor settings are changed accordingly.
*Test mode defaulted settings
Daylight sensor=disable
Hold time=3s
Twilight time=N/A
Twilight level=N/A
In this mode, when used for on/off control, after motion detected, sensor enters into a cycle of 3s on and 2s off. In this mode, when used for tri-level dimming control, after motion detected, sensor enters into a cycle of 3s on and 2s off(0.5s soft off + 1.5s off).
5V/12V DC Input Microwave Motion Sensor - Standard Version
DC Input Motion Sensor Module
Adjustable Motion Sensor Module
HNS101
5.8GHz C-band microwave.
Input voltage 12V DC (5V & 24V DC version available on request).
Input current:25mA.
5V DC high-low voltage output signal.
Features
5.8GHz C-band microwave.
Input voltage 12V DC (5V & 24V DC version available on request).
Input current:25mA.
5V DC high-low voltage output signal.
Super compact, flexible to be integrated into any suitable fixtures.
Dual-PD technology, r eal Lux-Off function for built-in application.
8 pin DIP switch setting, multiple options to meet different customer demands. Detection range up to 12m in diameter.
Mounting height: 3~6m.
RoHS compliant.
Settings
Detection range
Detection range can be reduced by selecting the combination on the DIP switches to fit precisely each application.
Hold-time
Hold-time means the time period to keep the lamp on 100% after motion detected.
*when hold-time set as 3s, sensor enters into test mode, this test mode is mainly for users to choose the desired detection range. In this mode, the daylight sensor is disabled, when there is no motion, fixture keeps off, when there is motion detected, fixture keeps a cycle of 3s on and 2s off.
Daylight sensor
Daylight sensor means the daylight threshold� to enable or disable the sensor function.
"Disable":The sensor works always, even during daylight. w50lux, 25lux": The sensor works only in twilight.
"10lux, 2lux": The sensor works only in the dark.
Description
Falcon is a radar sensor, which uses microwave doppler technology for activation of door. It can be mounted on all types of standard automatic doors. Falcon 2.0 is with unidirectionality function, to reduce the heat loss from building and save energy.
Function and Advantages
radar motion sensor for automatic door
Unidirectional and bidirectional detection optional
Intelligently opening & closing
High sensitivity and accuracy
For all kinds of automatic doors
TABLE OF SPECIFICATIONS
Technology: Microwave doppler radar
Transmitter frequency: 24.150 GHz
Transmitter radiated power: < 20 dBm EIRP
Transmitter power density: < 5 mW/cm�²
Min. detection speed: 5 cm/s
Supply voltage: 12V - 24V AC -/+10% 12V -24V DC +30%/-10%
Mains frequency: 50 Hz - 60 Hz
Max power consumption: < 2 W
Output: solid state relay(free of potential change-over contact
Current max.output: 2A(MAX)
Degree of Protection: IP54
Mounting height: 1.8 m to 5 m
Temperature range: -25'C TO +70'c
Dimensions: 80 mmï¼?L) * 60 mm(H)* 50 mm (W)
Angle of inclination: 0' to 90' (vertical direction); -30' to + 30' lateral direction)
Cable length: 3 M
Sq Type Microwave Motion Sensor
Product Size : 5.5 x4x 2.5 cm Adjustable Function: Time delay (8 Sec to 12 Min), Sensitivity (1-8m Radii), Light Setting (2-2000 Lux)
18 Months Mfg Warranty
Detection angle: 360/ Rated load: 1200Watt/Ideal installation height: 2 - 4 m. HF system : 5.8GHz CW radar,ISM band, Connection Point: L:- Phase/Line, N - Neutral i.e. (commaon for Both I/p and O/p) and L':- Load/to light
This microwave motion sensor reflects the development in interior lighting technology and provides close to zero energy wastage in terms of lights being on unnecessarily
Standard Motion Sensor Module
DC Input Motion Sensor Module
5V/12V DC Input Microwave Motion Sensor - Standard Version
HNS102
5.8GHz C-band microwave, tri-level dimming function.
Input voltage: 12V DC (5V & 24V DC version available on request).
Input current: 25mA.
Features
5.8GHz C-band microwave, tri-level dimming function.
Input voltage: 12V DC (5V & 24V DC version available on request).
Input current: �?� 25mA.
0~10V DC dimming output signal.
Super compact, flexible to be integrated into any suitable fixtures.
Dual-PD technology, real Daylight monitoring function for built-in application.
8 pin DIP switch setting, multiple options to meet different customer demands.Â
Detection range up to 12m in diameter.
Mounting height: 3~6m.
Operation temperature: -20�??~ +70�?? .
RoHS compliant.
Detection range
Detection range can be reduced by selecting the combination on the DIP switches to fit precisely each application.
Hold-time
Hold-time means the time period to keep the lamp on 100% after motion detected.
*when hold-time set as 3s# sensor enters into test mode, this test mode is mainly for users to choose the desired detection range. In this mode, the daylight sensor is disabled, when there is no motion, fixture keeps off, when there is motion detected, fixture keeps a cycle of 3s on and 2s off.
Daylight sensor
Daylight sensor means the daylight threshold to enable or disable the sensor function.
"Disable": The sensor works always, even during daylight.
w50lux": The sensor works only in twilight.
w10lux, 2luxw: The sensor works only in the dark.
Stand-by period
This is the time period that the lamp remains at a low light level before it is completely switched off in the long absence of people.
means bi-level dimming control, the fixture never switch off.
Stand-by dimming level
This is the dimmed low light level you would like to have after the hold-time in the absence of people.
5V/12V DC Input Microwave Motion Sensor Highbay Version
DC Input Motion Sensor Module
Highbay DC Input Motion Sensor
HNS111HB
5.8GHz C-band microwave.
Input voltage 12V DC (5V & 24V DC version available on request).
Input current:25mA.
Features
5.8GHz C-band microwave.
Input voltage 12V DC (5V & 24V DC version available on request).
Input current:25mA.
0~10V DC output signal
Super compact, flexible to be integrated into any suitable fixtures.
Dual ï¹£ PD technology, real Daylight monitoring function for built-in application.
IR remote commissioning, easy setting and user friendly.
Detection range up to 18m in diameter.
Mounting height: 10~12m.
Operation temperature: -20 ~ +70
RoHS compliant.
Settings(Remote control IR12)
Permanent ON/OFF function
Press ON/OFF button, fixture goes to permanent on or permanent off mode, sensor is disabled.
*press "Auto" ,"Reset" or "Ambient learn" to quit this mode.
Dim +/-
Press "Dim" button to automatically dim up or down the light brightness during hold-time from 10% to 100%. Another press to lock it down when desired brightness is achieved.
*after desired brightness is locked down, if user wants to dim again reversely, just press the Dim button again and then lock down the new brightness again.
Sensor mode
Press "Auto" button, the sensor starts to work and all settings remain the same as the latest status before the light was switched on/off.
Reset function
Press "Reset" button, all settings go back to factory default settings.
Factory default settings
Sensitivity=100%
Daylight sensor=disable
Hold time=90s
Twilight time=5min
Twilight level=10%
Ambient learn
Press "Ambient learn" button, the latest surrounding lux value overwrites previous lux value learned, and set as the daylight threshold. This feature enables the fixture to function well in any real application circumstance.
Test mode
"Test mode" is for testing purpose only, for users to check the functionality and choose the desired detection range. The sensor goes to test mode automatically after pressing this button.
Users can quit this mode by pressing "ON/OFF", "Reset' or any button of "Hold time". The sensor settings are changed accordingly.
*Test mode defaulted settings
Daylight sensor=disable
Hold time=3s
Twilight time=N/A
Twilight level=N/A
In this mode, when used for on/off control, after motion detected, sensor enters into a cycle of 3s on and 2s off. In this mode, when used for tri-level dimming control, after motion detected, sensor enters into a cycle of 3s on and 2s off(0.5s soft off + 1.5s off).
DC Input Motion Sensor Module
Standard Motion Sensor Module
5V/12V DC Input Microwave Motion Sensor - Standard Version
HNS101D
5.8GHz C-band microwave, tri-level dimming function.
Input voltage 12V DC (5V & 24V DC version available on request).
Input current:25mA.
Features
5.8GHz C-band microwave, tri-level dimming function.
Input voltage 12V DC (5V & 24V DC version available on request).
Input current:25mA.
5V DC PWM output or 0~10V DC signal.
Super compact, flexible to be integrated in t o any suitable fixtures.
Dual-PD technology, real Daylight monitoring function for built-in application.
8 pin DIP switch setting, multiple options to meet different customer demands.
Detection range up to 12m in diameter.
Mounting height: 3~6m.
Operation temperature; -20? ~ + 70?.
RoHS compliant.
Settings
Detection range
Detection range can be reduced by selecting the combination on the DIP switches to fit precisely each application.
Hold-time
Hold-time means the time period to keep the lamp on 100% after motion detected.
*when hold-time set as 3s, sensor enters into test mode, this test mode is mainly for users to choose the desired detection range. In this mode, the daylight sensor is disabled, when there is no motion, fixture keeps off, when there is motion detected, fixture keeps a cycle of 3s on and 2s off.
Daylight sensor
Daylight sensor means the daylight threshold to enable or disable the sensor function.
"Disable": The sensor works always, even during daylight.
w50lux": The sensor works only in twilight.
w10lux, 2luxw: The sensor works only in the dark.
Stand-by period
This is the time period that the lamp remains at a low light level before it is completely switched off in the long absence of people.
?+? means bi-level dimming control, the fixture never switch off.
Stand-by dimming level
This is the dimmed low light level you would like to have after the hold-time in the absence of people.
Daylight monitoring function
Utilizing the Dual-PD technology, this sensor can tell the difference of natural light and artificial light(lamp) from behind the diffuser, switch on automatically(even without movements) when the ambient light is below target value, and then switch off automatically whenever the artificial light is not required(ambient light is bright enough).
This is the REAL & INTELLIGENT daylight monitoring sensor for built-in installation.
Note: Lux-Off sampling time?30s; Lux-On sampling time?10s.
Lux-On function takes effect only when standby dimming period set at+?