Please click here to check who's online and chat with them.

Td 40.5Kv 1600A 25Ka Vacuum Interrupter For Vcb

Supplier From China
Aug-17-16

1. Brief introduction
TD 33KV 36kv 1600A 25KA (JUC632) vacuum interrupter for VCB
The interrupter adoption porcelain and ceramics lagging makes to insulate the outer shell. Contact is CuCr metal alloy material advanced technique of cup construction, break the discharge big. Insulate the level high, breaking the abiliting strong, the life span is long, mainten anle is sample, no explosion dangerous, no contaminate and the noise is low. The load switch main used electric power, machine, coal mine, chemical engineering, petroleum metallurgy etc. power transmission system used control with protect. more than keeping with at the multifarious operation.

Rated voltage: 33KV 36KV
Rated current: 1600A
Rated short-circuit breaking current: 25KA
Rated short-circuit making current: 63KA
Rated peak withstand current: 63KA
Rated short-time withstand current: 25KA
Rated short-circuit continuous time: 4 s
Rated single capacitor unit breaking current: 630A
Rated back to back capacitor unit breaking current: 400A
Rated short-time (1 min) withstand voltage: 95 KV
Rated contact pressure time-limit loop resistive: =25µO
Rated short-circuit breaking current breaking times: 30 Ops
Rated lightning impulse withstand voltage: 185 KV
Mechanical life: 10,000 Ops
Contact automatic: 200±50 N
Force required to hold contacts open at full stroke: 300±50 N
Contact-wear allowance thickness: 3 mm
Internal gas pressure: =1.33×10-3 Pa
Shelf life: 20 years

Price and Minimum Quantity

Price: $470
MOQ: Not Specified

Recent User Reviews

This user has not received any reviews yet!

Verification Status


 
 
Contact Supplier
Renew

More Items Similiar to: Td 40.5Kv 1600A 25Ka Vacuum Interrupter For Vcb

GOLD Member
Nov-15-22
Supplier From Shanghai, China
GOLD Member
Nov-23-22
Supplier From Mumbai, Maharashtra, India
Aug-17-16
 
Model No.: TD 12kv 1600A 31.5KA (JUC618A) vacuum interrupter for VCB
Main technical parameters
Rated voltage: 12 KV
Rated current: 1600A
Rated power frequency withstand voltage: 42 KV
Rated lightning impulse withstand voltage: 75 KV
Rated short circuit breaking current: 31.5KA
Rated short circuit making current(peak value): 80KA
Breaking operations under rated short circuit breaking current: 30 times
Rated short time withstand current: 31.5KA
Rated withstand current(peak value): 80KA
Rated duration of short circuit: 4 s
Mechanical life: 20,000 times
Closing force due to bellows and atmosphere: 120±50 N
Force required to hold contacts opening at full stroke: 190±50 N
Circuit resistance at lowest rated contacts force: =20µO
Storage life: 20 years
Limiting abrasion of contacts: 3 mm

Mechanical requiements of vacuum circuit breaker
Clearance between opening contacts: 11±1 mm
Average opening speed(Contacts closing position~75% contacts opening distance): 1.1±0.2 m/s
Average closing speed(30% contacts opening distance~contacts closing position): 0.6±0.2 m/s
Rated contacts pressure: 3150±200 N
Contacts bouncing duration at closing operation: =2 ms
Contacts re-bouncing clearance at opening operation: =2 mm
Synchronism of three phases: =1 ms
Aug-17-16
 
Model No.: TD 12kv 1600A 31.5A (JUC619) vacuum interrupter for VCB
Main technical parameters
Rated voltage: 12 KV
Rated current: 1600A
Rated power frequency withstand voltage: 48 KV
Rated lightning impulse withstand voltage: 85 KV
Rated short circuit breaking current: 31.5KA
Rated short circuit making current(peak value): 80KA
Breaking operations under rated short circuit breaking current: 30 times
Rated short time withstand current: 31.5KA
Rated withstand current(peak value): 80KA
Rated duration of short circuit: 4 s
Mechanical life: 10,000 times
Closing force due to bellows and atmosphere: 120±50 N
Force required to hold contacts opening at full stroke: 190±50 N
Circuit resistance at lowest rated contacts force: =20µO
Storage life: 20 years
Limiting abrasion of contacts: 3 mm

Mechanical requiements of vacuum circuit breaker
Clearance between opening contacts: 11±1 mm
Average opening speed(Contacts closing position~75% contacts opening distance): 1.1±0.2 m/s
Average closing speed(30% contacts opening distance~contacts closing position): 0.6±0.2 m/s
Rated contacts pressure: 3150±200 N
Contacts bouncing duration at closing operation: =2 ms
Contacts re-bouncing clearance at opening operation: =2 mm
Synchronism of three phases: =1 ms
* It Needs additional insultating protection.
VERIFIED
Feb-08-22
Supplier From Singapore, Singapore
GOLD Member
VERIFIED
Jun-27-24

Electric Motors And Alternators

$180
MOQ: 10  Tons (UK)
Sample Available
Supplier From Ontario, Canada
 
Top Quality Compressor Scrap Used Electric Motor scrap AC Compressor Scrap


Drained Copper Compressor â?? Fridges/AC (RAINS per ISRI Specifications).

Our copper content on 99.97 %

Monthly Supply Capacity: 500 - 1500 metric tons,

Type: Fridges, AC.

Packaging Detail: Wood Pallets, 20(40) FCL/ According to ISRI Specification in Containers

Quantity: Between 200~500MT per month

Minimum Order acceptable 1x20FCL (25MT or 26MT/20FCL, 3000 or 3450 Pieces/20FCL



Detailed Specifications :

Compressor Brands : Necchi, Danfoss, Aspera, Ireland, Embraco

Compressor Weight : 2kg, 4kg, 6kg, 8kg, 10kg, and 12kg

More Details : 220-240 v 50 or 60 hz.

Cooling capacity: 90-190 w displ

Size : 5.99 -12.53 cm3

Purity: 99.98% copper inside with connection box

Send your message to this supplier

Main Specification:
Aug-17-16
 
Model No.: TD 12kv 1250A 25KA (JUC613) vacuum interrupter for VCB
Main technical parameters
Rated voltage: 12 KV
Rated current: 1250A
Rated power frequency withstand voltage: 42 KV
Rated lightning impulse withstand voltage: 75 KV
Rated short circuit breaking current: 25KA
Rated short circuit making current(peak value): 63KA
Breaking operations under rated short circuit breaking current: 30 times
Rated short time withstand current: 25KA
Rated withstand current(peak value): 63KA
Rated duration of short circuit: 4S
Mechanical life: 20,000 times
Closing force due to bellows and atmosphere: 120±50N
Force required to hold contacts opening at full stroke: 190±50N
Circuit resistance at lowest rated contacts force: =20µO
Storage life: 20 years
Limiting abrasion of contacts: 3 mm

Mechanical requiements of vacuum circuit breaker
Clearance between opening contacts: 11±1mm
Average opening speed(Contacts closing position~75% contacts opening distance): 1.1±0.2 m/s
Average closing speed(30% contacts opening distance~contacts closing position): 0.6±0.2 m/s
Rated contacts pressure: 2000±200N
Contacts bouncing duration at closing operation: =2ms
Contacts re-bouncing clearance at opening operation: =2mm
Synchronism of three phases: =1ms
Aug-17-16
 
Model No.: TD 12kv 1250A 31.5KA (JUC618) vacuum interrupter for VCB
Main technical parameters
Rated voltage: 12 KV
Rated current: 1250A
Rated power frequency withstand voltage: 42 KV
Rated lightning impulse withstand voltage: 75 KV
Rated short circuit breaking current: 31.5KA
Rated short circuit making current(peak value): 80KA
Breaking operations under rated short circuit breaking current: 30 times
Rated short time withstand current: 31.5KA
Rated withstand current(peak value): 80KA
Rated duration of short circuit: 4S
Mechanical life: 20,000 times
Closing force due to bellows and atmosphere: 120±50N
Force required to hold contacts opening at full stroke: 190±50N
Circuit resistance at lowest rated contacts force: =20µO
Storage life: 20 years
Limiting abrasion of contacts: 3 mm

Mechanical requiements of vacuum circuit breaker
Clearance between opening contacts: 11±1 mm
Average opening speed(Contacts closing position~75% contacts opening distance): 1.1±0.2 m/s
Average closing speed(30% contacts opening distance~contacts closing position): 0.6±0.2 m/s
Rated contacts pressure: 3150±200 N
Contacts bouncing duration at closing operation: =2 ms
Contacts re-bouncing clearance at opening operation: =2 mm
Synchronism of three phases: =1 ms
Aug-17-16
 
Model No.: TD 12kv 1250A 31.5KA (JUC619A) vacuum interrupter for VCB
Main technical parameters
Rated voltage: 12 KV
Rated current: 1250A
Rated power frequency withstand voltage: 48 KV
Rated lightning impulse withstand voltage: 85 KV
Rated short circuit breaking current: 31.5KA
Rated short circuit making current(peak value): 80KA
Breaking operations under rated short circuit breaking current: 30 times
Rated short time withstand current: 31.5KA
Rated withstand current(peak value): 80KA
Rated duration of short circuit: 4 s
Mechanical life: 10,000 times
Closing force due to bellows and atmosphere: 120±50 N
Force required to hold contacts opening at full stroke: 190±50 N
Circuit resistance at lowest rated contacts force: =20µO
Storage life: 20 years
Limiting abrasion of contacts: 3 mm

Mechanical requiements of vacuum circuit breaker
Clearance between opening contacts: 11±1 mm
Average opening speed(Contacts closing position~75% contacts opening distance): 1.1±0.2 m/s
Average closing speed(30% contacts opening distance~contacts closing position): 0.6±0.2 m/s
Rated contacts pressure: 3150±200 N
Contacts bouncing duration at closing operation: =2 ms
Contacts re-bouncing clearance at opening operation: =2 mm
Synchronism of three phases: =1 ms
* It Needs additional insultating protection.