All HIMA products mentioned in this manual are protected by the HIMA trade-mark. Unless noted otherwise, this also applies to other manufacturers and their respective products referred to herein. All of the instructions and technical specifications in this manual have been written with great care and effective quality assurance measures have been implemented to ensure their validity. For questions, please contact HIMA directly. HIMA appreciates any suggestion on which information should be included in the manual. Equipment subject to change without notice. HIMA also reserves the right to modify the written material without prior notice. The safety-related F35 controller is a compact system located in a metal enclosure with 24 digital inputs, 8 digital outputs, 2 counters and 8 analog inputs. The controller is available in 3 model variants for SILworX and 3 model variants for ELOP II Factory, see Chapter 3.2. All variants are described in this manual. The device is suitable for mounting in Ex-zone 2, see Chapter 4.1.5. The device has been certified by the TÃ??V for safety-related applications up to SIL 3 (IEC 61508, IEC 61511 and IEC 62061), Cat. 4 (EN 954-1) and PL e (EN ISO 13849-1). Further safety standards, application standards and test standards are specified in the certificate available on the HIMA website.
To supply the I/O racks the 5 V power supply with corresponding GND is available at the rear side of the central rack.
The 5 V DC power needed for the microprocessor system and as control current for the I/O modules is generated from the 24 V DC power of the system via clocked 24 V DC/ 5 V DC power supply modules bearing the F 7126 identification. One central rack can be equipped with a maximum of 3 power supply modules. The power supply modules are switched in parallel. One or two power supply modules are usually able to supply the PES. A further power supply module is used to increase availability.