Please click here to check who's online and chat with them.

Find Verified Rectifier Eltek Flatpack2 380 3000 He (Ui) Suppliers, Manufacturers and Wholesalers

Jan-07-22
Supplier From Dongguan, Guangdong, China
 
Flatpack2 380V Rectifier
Doc 241119.825.DS3 v4

Model Flatpack2 380/3000 HE (UI)
Part number 241119.825
INPUT DATA
Voltage (nominal) 176 - 277 VAC / 260 - 400 VDC1)
Voltage (range) 85 - 305 VAC / 260 - 410 VDC1)
Frequency 45 - 66 Hz / 15 - 18.5 Hz2) / DC1)
Current (maximum) @ nominal input, full load 18.2 ARMS
Power Factor > 0.99 at 50% load or more
Protection
Fuse in L & N
Varistor
Disconnect when VIN is out of range
OUTPUT DATA
Voltage (default) 381 VDC
Voltage (adjustable range) 300 - 400 VDC
# Pb cell supported 156 - 168 3)
Power continuous (maximum) 3000 W
Power @ 85 VAC / 85 VDC 1200 W
Current continuous (maximum) 9 A (@VOUT < 336 VDC) / 7.9 A (@ VOUT = 381 VDC)
Current sharing (10 - 100% load) ±5% of maximum current from 10 to 100% load
Static Voltage regulation (10 - 100% load) ±0.5%
Dynamic Voltage regulation ±2.0% for 10-90% or 90-10% load variation, regulation time < 10 ms 5)
Hold up time > 20 ms; output voltage > 300 VDC at 1500 W load
Ripple < 1000 mVP-P , 30 MHz bandwidth
Protection Overvoltage shutdown, Hot plug-in - Inrush current limiting, ORing diode, Fuse5), Short
circuit proof, High temperature protection, Overload shutdown4)
OTHER SPECIFICATIONS

Efficiency @ 230 VAC / 380VDC input 96.2% / 96.6%
Isolation 3.0 kVAC input to output, 1.5 kVAC input to earth, 1.5 kVDC output to earth,
3.0 kVAC CAN to primary, 3.0 kVAC CAN to secondary
Alarms (Red LED) Low mains shutdown, High and low temperature shutdown, Rectifier Failure, Overvoltage
shutdown on output, Fan failure, Low voltage alarm, CAN bus failure
Warnings (Yellow LED) Rectifier in power derate mode, Remote battery current limit activated, Input voltage out
of range, flashing at overvoltage
Normal (Green LED) Input and output ok
Acoustic noise, at nominal input and full load < 40dBA @Tambient< 25C / 40C
MTBF (Telcordia SR-232 Iss.3 Meth. II Case L1) 2 291 210h (@ Tambient = 25 C)
Operating temperature -40 to +75C (-40 to +167F), humidity 5 - 95% RH non-condensing
Output power de-rates linear from 3000W @ 50C (122F) to 980W @ 7C(167F)
Storage temperature -40 to +85C (-40 to +185F), humidity 0 - 99% RH non-condensing
Dimensions[WxHxD] / Weight 109 x 41.5 x 327 mm (4.25 x 1.69 x 13) / < 1.95 kg (4.3 lbs)
DESIGN STANDARDS
Electrical safety EN 60950-1:2006+A11:2009+A1:2010+A12:2011+A2:2013, IEC 60950-1:2013, UL
60950-1:2014, CSA C22.2 No. 60950-1-07
EMC EN 61000-6-1:2007, -6-2:2005, -6-3:2007 + A1:2010, -6-4:2007 + A1:2010,
IEC61000-6-5: 2015, EN 300 386:v1.6.1, FCC CFR 47 Part 15:2013
Environment
Tested according to: ETSI EN 300 019: 2-1 (Class 1.2) & 2-2 (Class 2.3)
Normal operating conditions as per IEC 62040-5-3:2016 clause 4.2. Other operating
conditions as per IEC 62040-5-3:2016 clause 4.3, must be advised
2011/65/EU (RoHS) & 2012/19/EU (WEEE)
Jan-08-22

Eltek Flatpack2 380/3000 He Ui

$100
MOQ: Not Specified
Supplier From Dongguan, Guangdong, China
 
Flatpack2 380/3000 HE UI 380V Rectifier 241119.825

HE rectifier for 380VDC in data centers
The Flatpack2 380/3000 HE UI rectifier has high efficiency, ORing protection on output, and high output power.
Distribute pure battery backup DC voltage with a minimum of loss. Remove the low reliable DC-AC step in the central backup power system and maximize its reliability and efficiency.
Stack cabinets with up to 72 rectifiers to build large power systems monitored by the Smartpack2 controller.
The rectifier's Universal Input also allows it to be powered from the 380Vdc bus. Static voltage outputs (300-400Vdc) can be realized for 400Vdc remote powering and other applications.
Jan-08-22
Supplier From Dongguan, Guangdong, China
 
ELTEK FLATPACK2 48V/3000W HE Rectifier Module 241119.903

INPUT DATA
Voltage (nominal) 176 - 275 VAC
Voltage (operating range) 85 - 300 VAC
Frequency 45 - 66 Hz
Current (maximum) 19 ARMS
Power Factor > 0.99 at 50-100% load
Protection Fuse in L & N, Varistor, Shutdown above 300 VAC
OUTPUT DATA
Voltage (default) 53.5 VDC
Voltage (adjustable range) 43.2 - 57.6 VDC
Power @ 230 VAC 3000 W
Power @ 85 VAC 1380 W
Current 62.5 A (@ 48 VDC)
Current sharing (10 - 100% load) �±5% of maximum current from 10 to 100% load
Static Voltage regulation (10 - 100% load) �±0.5%
Dynamic Voltage regulation �±5.0% for 10-90% or 90-10% load variation, regulation time < 50ms
Hold up time, 1500 W / 3000 W output power >20ms / >10ms ; output voltage > 43 VDC
Ripple < 150 mV peak to peak, 30 MHz bandwidth
Protection
Fuse, Short circuit proof, High temperature protection, Overvoltage shutdown,
Hot plug-in inrush current limiting
Jan-08-22
Supplier From Dongguan, Guangdong, China
 
ELTEK Flatpack2 24/1800 HE 24V Rectifier
Dec-30-21
Supplier From Dongguan, Guangdong, China
 
Original Eltek Rectifier Module Flatpack2 48/1500 HE SOLAR
212 Rectifier Eltek Flatpack2 380 3000 He (Ui) Suppliers
Short on time? Let Rectifier Eltek Flatpack2 380 3000 He (Ui) sellers contact you.
Jan-08-22
Supplier From Dongguan, Guangdong, China
 
ELTEK Flatpack2 HVDC/DC Converter DCDC 380/48 3000 SHE

INPUT DATA
Voltage (nominal) 381 VDC
Voltage (operating range) 260 - 400 VDC
Maximum current 12.3 ADC
Protection Fuse, shutdown when VIN is out of range
OUTPUT DATA
Voltage (default) 54.5 VDC
Voltage (adjustable range) 50 - 55 VDC
Max power, nominal input 3000 W
Max current, @VOUT = 50 VDC 60 A
Current sharing �±5% of maximum current from 10 to 100% load
Static voltage regulation �±0.5% from 0 - 100% load and nominal input
Dynamic voltage regulation �±5.0% for 10-90% or 90-10% load variation, regulation time < 50ms
Ripple < 150 mVPP , 30 MHz bandwidth
Protection Overvoltage shutdown, short circuit proof, high temperature, hot plug-in
inrush current limiting, OR-ing FET
Jan-08-22
Supplier From Dongguan, Guangdong, China
 
36/1000 HE UI
ELTEK Flatpack S rectifier 36/1000 HE UI 241122.235

INPUT DATA
Voltage (nominal) 185 - 400 VDC / 185 - 275 VAC
Voltage (operating range) 85 - 400 VDC / 85 - 305 VAC
Frequency DC, 16 2/3 Hz, 45 - 66 Hz
Current (maximum) 5.9 ADC / 5.9 ARMS
Protection Fuse in Positive & Negative, Reversed polarity insensitive, Shutdown above 420 VDC / 305 VAC
OUTPUT DATA
Voltage 40 VDC
Voltage (adjustable range) 331) - 45 VDC
Power (maximum) @ nominal input 1000 W / 450 W @16 2/3 Hz input
Power (maximum) @ 85 VDC / 85 VAC input 440 W / 440 W
Current (max cont.) @ nominal input 27.8 A (@VOUT < 36 VDC)
Hold up time, maximum output power >10ms; output voltage > 33 VDC
Current sharing (10 - 100% load) �±5% of maximum current from 10 to 100% load
Static Voltage regulation (10 - 100% load) �±0.5%
Dynamic Voltage regulation �±5.0% for 10-90% or 90-10% load variation, regulation time < 50ms
Ripple < 150 mVPP , 30 MHz bandwidth
Protection
ORing FET
Short circuit proof
High-temperature protection
Overvoltage Shutdown
Jan-08-22
Supplier From Dongguan, Guangdong, China
 
ELTEK Flatpack S 36/1000 HE UI rectifier

Applications in these markets demand state-of-the-art, reliable, and safe DC power systems. Flatpack S delivers an industry-leading power density in its segment, many safety functions, a wide operating temperature range, and superb reliability in its small 217mm deep housing.
Used in the 3U rack with Smartpack S controller, the Flatpack S rectifiers cover 2 to 8kW applications using a minimum of space, less than 18 liters, and low heat dissipation.
GOLD Member
VERIFIED
Oct-25-20
Supplier From Rajkot, Gujarat, India
 
Monoblock pumps -
Falcon centrifugal monoblock pumpsets are powered by a totally enclosed fan cooled AC induction two pole motor. Motor stator is made of low watt loss silicon steel laminations assembled under pressure and rigidly locked in the
frame. The windings are of high-grade enameled copper wire offer excellent resistance and are varnish impregnated. Construction of motor frame and usage of quality materials result in high performance and low temperature rise
thereby increasing the life cycle of the motor.

salient features
- High operating efficiency resulting in lower power consumption
- Good suction lift characteristics
- Inbuilt thermal overload protector in al single phase pumpsets upto 2.0 HP
- Specially designed for wide voltage operation
- Dynamically balanced rotating parts including rotor and impeller ensures minimum vibration and longer life
- Back pull-out design for easy servicing and repair
- Double shielded ball bearings, so no need of external lubrication
- All Model fitted to Mechanical seal.

specification
- Power Range : 0.37Kw - 1.5 Kw (0.5 HP - 2.0 HP)
- Version : Single Phase, 220-240V, 50Hz AC Supply
Three Phase, 380-415V, 50Hz AC Supply
- Speed : 2880 RPM
- Maximum Total Head : 32 Mtr.
- Maximum Flow Rate : 940 LPM
- Maximum Suction Lift : 7 Mtr.
- Degree of Protection : IP 44
- Class of Insulation : B0
- Maximum Ambient Tem. : 40 C
- Sealing : Mechanical Seal
- Type of Duty : S1 (Continuous)
- Method of Starting : Permanent Split Capacitor (PSC)
- Direction of Rotation : Three Phase, Electrically Reversible
- Nominal Pumpset Size (Suction X Delivery in inch) : 25 X 25, 32 X 25, 40 X 32, 40 X 40, 50 X 40,
50 X 50, 65 X 50, 80 X 65, 80 X 80 (All size in mm)

characteristics of clear cold water
- Maximum liquid temperature : 33C max
- Permissible amount of sand : 25 g/m
- Allowable solids : 3000 ppm (max.)
- Chloride ion density : 500 ppm (max.)
- Turbidity : 50 ppm silica scale (max.)
- Hardness (Drinking Water) : 300 ppm (max.)
- Specific gravity : 1.004 (max.) 6
- Viscosity : 1.75 x 10 m/sec (max.)
- Ph Value : 6.5 to 8.5
Part Name Material
Mechanical Seal : Carbon & Ceramic
Motor Shaft : EN-8
Motor Body : FG-250
Bearing : SKF
End Cover : FG-250
Bracket : FG-250
Flange : FG-250
Casing : FG-250
Impeller : FG-250
Cooling Fan : Plastic
GOLD Member
VERIFIED
Oct-25-20
Supplier From Rajkot, Gujarat, India
 
Monoblock Pumps
Falcon centrifugal monoblock pumpsets are powered by a totally enclosed fan cooled AC induction two pole motor. Motor stator is made of low watt loss silicon steel laminations assembled under pressure and rigidly locked in the
frame. The windings are of high-grade enameled copper wire offer excellent resistance and are varnish impregnated. Construction of motor frame and usage of quality materials result in high performance and low temperature rise
thereby increasing the life cycle of the motor.

salient features
High operating efficiency resulting in lower power consumption
- Good suction lift characteristics
- Specially designed for wide voltage operation.
- Dynamically balanced rotating parts including rotor and impeller ensures minimum vibration and longer life.
- Back pull-out design for easy servicing and repair.
- Double shielded ball bearings, so no need of external lubrication.
- Mechanical seal is provided as per customers requirement

Specification
- Power Range : 2.2 Kw - 11.2 Kw (3.0 HP - 15.0 HP)
- Version : Three Phase, 380-415V, 50Hz AC Supply
- Speed : 2880 RPM
- Maximum Total Head : 65 Mtr.
- Maximum Flow Rate : 1450 LPM
- Maximum Suction Lift : 7 Mtr.
- Degree of Protection : IP 44
- Class of Insulation : B0
- Maximum Ambient Tem. : 40 C
- Sealing : Stuffing Box
- Type of Duty : S1 (Continuous)
- Direction of Rotation : Three Phase, Electrically Reversible
- Nominal Pumpset Size (Suction X Delivery in inch) : 50 X 40, 50 X 50, 65 X 50, 80 X 65, 80 X 80
100 X 80 and 100 X 100 (All size in mm)

Characteristics Of Clear Cold Water
- Maximum liquid temperature : 33C max
- Permissible amount of sand : 25 g/m
- Allowable solids : 3000 ppm (max.)
- Chloride ion density : 500 ppm (max.)
- Turbidity : 50 ppm silica scale (max.)
- Hardness (Drinking Water) : 300 ppm (max.)
- Specific gravity : 1.004 (max.) 6
- Viscosity : 1.75 x 10 mÃ?/sec (max.)
- Ph Value : 6.5 to 8.5

Material of construction - motor
Part Name Material
Gland Dori : Graphite String
Motor Shaft : EN-19 with SS SLEEVE
Motor Body : FG-250
Bearing : SKF
End Cover : FG-250
Bracket : FG-250
Flange : FG-250
Casing : FG-250
Impeller : FG-250
Cooling Fan : Aluminium
GOLD Member
VERIFIED
Oct-25-20
Supplier From Rajkot, Gujarat, India
 
Monoblock pumps
Falcon centrifugal monoblock pumpsets are powered by a totally enclosed fan cooled AC induction two pole motor. Motor stator is made of low watt loss silicon steel laminations assembled under pressure and rigidly locked in the
frame. The windings are of high-grade enameled copper wire offer excellent resistance and are varnish impregnated. Construction of motor frame and usage of quality materials result in high performance and low temperature rise
thereby increasing the life cycle of the motor.

Salient Features
High operating efficiency resulting in lower power consumption.
- Good suction lift characteristics.
- Specially designed for wide voltage operation.
- Dynamically balanced rotating parts including rotor and impeller ensures minimum vibration and longer life.
- Back pull-out design for easy servicing and repair.
- Double shielded ball bearings, so no need of external lubrication.

specification
- Power Range : 1.5 Kw - 5.5 Kw (2.0 HP - 7.5 HP)
- Version : Three Phase, 380-415V, 50Hz AC Supply
- Speed : 1440 RPM
- Maximum Total Head : 12 Mtr.
- Maximum Flow Rate : 3160 LPM
- Maximum Suction Lift : 7 Mtr.
- Degree of Protection : IP 44
- Class of Insulation : B0
- Maximum Ambient Tem. : 40 C
- Sealing : Stuffing Box
- Type of Duty : S1 (Continuous)
- Direction of Rotation : Three Phase - Electrically Reversible
- Nominal Pumpset Size (Suction X Delivery in inch) : 80 X 80, 100 X 100, 125 X 125, 150 X 150
(All size in mm)

Characteristics Of Clear Cold Water
- Maximum liquid temperature : 33C max
- Permissible amount of sand : 25 g/m
- Allowable solids : 3000 ppm (max.)
- Chloride ion density : 500 ppm (max.)
- Turbidity : 50 ppm silica scale (max.)
- Hardness (Drinking Water) : 300 ppm (max.)
- Specific gravity : 1.004 (max.) 6
- Viscosity : 1.75 x 10 m/sec (max.)
- Ph Value : 6.5 to 8.5
Part Name Material
Gland Dori : Graphite String
Motor Shaft : EN-19 with SS SLEEVE
Motor Body : FG-250
Bearing : SKF
End Cover : FG-250
Bracket : FG-250
Flange : FG-250
Casing : FG-250
Impeller : FG-250
Cooling Fan : Aluminum
Dec-30-21

Eltek Flatpack2 24/1800 He

$100
MOQ: Not Specified
Supplier From Dongguan, Guangdong, China
 
Eltek Rectifier Module Flatpack2 24/1800 HE
Dec-30-21

Eltek Flatpack2 220/2000 He

$100
MOQ: Not Specified
Supplier From Dongguan, Guangdong, China
 
Eltek Rectifier Module Flatpack2 220/2000 HE
Jan-07-22

Eltek Flatpack2 48/3000 She

$333
MOQ: Not Specified
Supplier From Dongguan, Guangdong, China
 
Eltek Flatpack2 48/3000 SHE 241119.106
The Flatpack2 48V Super HE rectifiers are contributing to setting the new industry standard for efficiency in the DC power market.
With an efficiency of 97.8%, the Super HE is a premium rectifier particularly suitable for markets and applications where the energy is costly. In grid-connected applications, the payback time is down to 2 years compared to standard HE rectifiers, and in hybrid applications even faster.
The Flatpack2 Super HE is fully compatible with Flatpack2 and Flatpack2 HE systems and can replace any Flatpack2 48V rectifier module.
Jan-08-22
Supplier From Dongguan, Guangdong, China
 
Eltek Faltpack2 60/2000 HE SOLAR CHARGER MODULE

Model 60/2000 HE SOLAR
Part number 241115.675
INPUT DATA
Voltage (nominal) 185 - 275 VDC
Voltage (operating range) 85 - 300 VDC
Voltage (start-up) 150 VDC
Current (maximum) 11.6 ARMS
Protection Fuse in + & -, Varistor, Reversed Polarity
OUTPUT DATA
Voltage (default) 67 VDC
Voltage (adjustable range) 52.5 - 72 VDC1)
Power (maximum) 2000 W
Power @ 85 VDC (maximum) 850 W
Current (maximum) 33.3 A (@ 60 VDC)
Current sharing (10 - 100% load) Passive to optimize power available from each string of solar panels
Static Voltage regulation (10 - 100% load) �±0.5%2)
Dynamic Voltage regulation �±5.0% for 10-90% or 90-10% load variation, regulation time < 50ms
Ripple < 250 mV peak to peak, 30 MHz bandwidth
Protection Fuse, Short circuit proof, High-temperature protection, Overvoltage shutdown,
Hot plug-in inrush current limiting
Dec-30-21

Eltek Flatpack2 48/2000 He Module

$100
MOQ: Not Specified
Supplier From Dongguan, Guangdong, China
 
Original Rectifier Module Flatpack2 48/2000 HE
Jun-09-20
 
Flatpack2 48V 2000W Super HE Eltek Rectifier Module 241119.106

APPLICATIONS

TELECOM - WIRELESS
Radio base station / Cell sites
LTE / 4G / WiMAX
Mobile switching center (MCS)
Microwave
Broadband
TELECOM - FIXED
Central office
Telephony servers / switches
Fiber optics
Microwave
Broadband
Broadcast
Data center

Key Features

SUPER HIGH EFFICIENCY â?? 97.8%
HIGH POWER DENSITY â?? 33 W/IN3
COMPATIBLE WITH EXISTING SYSTEMS
GLOBAL COMPLIANCE
PATENTED TECHNOLOGY
HOT PLUGGABLE

Super High Efficiency (SHE) rectifiers for Telecom applications

The Flatpack2 48V Super HE rectifiers are contributing to setting the new industry standard for efficiency in the DC power market.
With an efficiency of 97.8% the Super HE is a premium rectifier particularly suitable for markets and applications where the energy is costly. In grid connected applications the payback time is down to 2 years compared to standard HE rectifiers, and in hybrid applications even faster.
The Flatpack2 Super HE is fully compatible with Flatpack2 and Flatpack2 HE systems and can replace any Flatpack2 48V rectifier module.

Specifications

Model 48/3000 SHE
Part number 241119.106
INPUT DATA
Voltage (nominal range) 206 - 264 VAC
Voltage (operating range) 85 - 264 VAC
Frequency 45 - 66 Hz
Maximum current 16 ARMS
Protection Fuse in Live, varistor for transient protection, shutdown when VIN is out of range
Jun-09-20
 
High efficiency and reliable rectifiers
The most efficient power conversion module in the industry! Since the launch the Flatpack2 family has expanded into a wide selection of power ratings and voltages.
Power systems up to the MW-range can be realized using the 10A model addressing small and larger modular data centersâ?? power needs. 220VDC power systems provide an excellent alternative to traditional AC UPS providing significant efficiency and reliability improvements.
With 220V DC, standard components, cables and distribution can be used and most IT equipment designed for 208/ 230V AC can be connected directly to the 220V DC bus.

Applications

Power Utilities
Switch Tripping
Control & Protection Systems
Emergency Lighting
Railway Infrastructure
Converter Stations
Power Stations
Marine And Off-Shore
Central Power System
Data Center
Central Power System
Dc/ Dc - Isolate Branches

Specifications

Part number 241115.815
Model 220 / 2000 HE WOR
INPUT DATA
Voltage range 85 - 300 V AC/ DC
Voltage range (nominal) 185 - 275 V AC/ DC
Frequency 0 - 66 Hz
Maximum current 11.9 A RMS
Power Factor 0.99 (@ 50-100% load)
THD (@ 230 VAC) < 5 % (@ full load)
Protection Varistor for transient protection, fuse in both lines, shutdown above 300/ 305 V
OUTPUT DATA
Default voltage 245.3 V DC
Voltage range 178.5 1) - 297 VDC
Jun-09-20
 
Model 48/2000 SHE
Part number 241115.106
INPUT DATA
Voltage (nominal range) 185 - 264 VAC
Voltage (operating range) 85 - 264 VAC
Frequency 45 - 66 Hz
Maximum current 11.6 ARMS
Protection Fuse in Live, varistor for transient protection, shutdown when VIN is out of range
OUTPUT DATA
Voltage (default) 53.5 VDC
Voltage (adjustable range) 43.21) - 57.6 VDC
Max power, nominal input 2000 W
Max power, de-rated @VIN = 85 VAC 850 W
Max current, @VOUT = 48 VDC 41.7 A
Current sharing �±5.0% of max current
Static voltage regulation (10-100% load) �±0.5%
Dynamic voltage regulation 5.0% for 10-90% or 90-10% load variation, regulation time < 50ms
Hold up time (3000W load) >10ms; output voltage > 42 VDC
Ripple
Jun-09-20
 
Model 48V / 2000W HE
Part number 241115.105
INPUT DATA
Voltage (nominal) 185 - 275 VAC / 185 - 275 VDC
Voltage (range) 85 - 300 VAC / 85 - 275 VDC
Frequency 45 - 66 Hz, 15-18.5 Hz1) / 0 Hz
Current (maximum) @ nominal input, full load 11.6 ARMS
Protection Fuse in both lines Varistor for transient protection Disconnect above 300 VAC/DC
OUTPUT DATA
Voltage (default) 53.5 VDC
Voltage (adjustable range) 43.5 - 57.6 VDC
Power (maximum) 2000 W
Power @ 85 VAC 850 W
Current (maximum) @ nominal input, full load 41.7 A
Ripple, 30MHz bandwidth < 100 mVpp
Psophometric noise < 2 mVRMS
Static Voltage regulation �±0.5% for 10 - 100% load
Dynamic Voltage regulation �±5.0% for 10-90% or 90-10% load variation, regulation time < 50ms
Protection Fuse, Short circuit proof, High temperature protection, Hot plug-in inrush current limiting
OTHER SPECIFICATIONS
Efficiency @ nominal input 96 %
Isolation 3.0 kVAC - input to output, 1.5 kVAC - input to earth, 500 VDC - output to earth
Alarms: Red LED 'on' Low mains shutdown, High and low temperature shutdown, Rectifier Failure, Overvoltage shutdown on output, Fan failure, Low voltage alarm, CAN bus failure
Warnings: Yellow LED 'on' Rectifier in power derate mode, Remote battery current limit activated, Input voltage out of range, flashing at overvoltage
Normal (module running): Green LED 'on'
Acoustic noise, full load @ Tambient = 25�°C
full load @ Tambient = 40�°C < 20 dBA
< 56 dBA
MTBF (Telcordia SR-332 Issue I method III (a)) >350 000 (@ Tambient : 25 �°C)
Operating temperature -40 to +75�°C (-40 to +167�°F)4), humidity 5 - 95% RH non-condensing
Temperature de-rating >55�°C (131�°F), 1200W @ 75�°C (167�°F)
Storage temperature -40 to +85�°C (-40 to +185�°F), humidity 0 - 99% RH non-condensing
Dimensions[WxHxD] / Weight 109 x 41.5 x 327mm (4.25 x 1.69 x 13â??) / 1.95 kg (4.3 lbs)
DESIGN STANDARDS
Electrical safety EN 60950-1:2006+A11:2009+A1:2010+A12:2011+A2:2013, UL 60950-1:2014, CSA C22.2 No.60950-1-07:2014, IEC 60950-1:2013
EMC EN 61000-6-1:2019, -6-2:2019, - 6-3:2007 + A1:2011, - 6-4:2019, EN 61000-3-2:2019 ETSI EN 300 386 V.2.1.1, Telcordia NEBS GR1089 CORE
Marine DNVGL-CG-03392)
Environment ETSI EN 300 019: 2-1 (Class 1.2) & 2-2 (Class 2.3) EU 2015/863 (RoHS) & 2012/19/EU (WEEE)
Normal operating conditions as per IEC 62040-5-3:2016 clause 4.2. Other operating conditions as per IEC 62040-5-3:2016 clause 4.3, must be advised
212 Rectifier Eltek Flatpack2 380 3000 He (Ui) Suppliers
Short on time? Let Rectifier Eltek Flatpack2 380 3000 He (Ui) sellers contact you.