1. General
HVJ5 1.14kv 125A AC vacuum contactor is designed for long-distance making and breaking of circuit, frequent starting and controlling of AC motors in the power systems, with AC 50Hz-60Hz, rated voltage of 1,140V and rated current to 125A. It also can be equipped with thermal relay and all kinds of protection apparatus like electromagnetic starter, especially applied to explosion-proof starter and so on.
2. Main technical parameter
Rated voltage: 1140 V
Control voltage: 36V, 110V, 220V, 380V
Rated current: 125A
Opening distance: 1.8±0.2 mm
Over travel: 1±0.2 mm
Final pressure: 30±3 N
Main circuit power frequency voltage withstand: 4200 V
Auxiliary circuit power frequency voltage withstand: 2500 V
Control circuit power frequency voltage withstand: 2000 V
Making capacity: 10Ie,100 times
Breaking capacity: 8Ie,25 times
Limit breaking current(A): 2000,3 times
Electricity life times AC3: 60*104
Electricity life times AC4: 60*104
Mechanical life times: 300*104
Overload capacity: 8Ie 10 S
Remark: “Ie” is Rated current of main circuit.
1. General HVJ5 1.14 kv 250A AC vacuum contactor is designed for long-distance making and breaking of circuit, frequent starting and controlling of AC motors in the power systems, with AC 50Hz-60Hz, rated voltage of 1140V and rated current to 250A. It also can be equipped with thermal relay and all kinds of protection apparatus like electromagnetic starter, especially applied to explosion-proof starter and so on. 2. Main technical parameter Rated voltage: 1140 v Control voltage: 36V, 110V, 220V, 380V Rated current: 250A Opening distance: 2±0.2 mm Over travel: 1±0.2 mm Final pressure: 30±3 N Main circuit power frequency voltage withstand: 4200 V Auxiliary circuit power frequency voltage withstand: 2500 V Control circuit power frequency voltage withstand: 2000 V Making capacity: 10Ie,100 times Breaking capacity: 8Ie,25 times Limit breaking current(A): 4500,3 times Electricity life times AC3: 60*104 Electricity life times AC4: 60*104 Mechanical life times: 300*104 Overload capacity: 8Ie 10S Remark: “Ie” is Rated current of main circuit.
1. General HVJ5 1.14 kv 1000A AC vacuum contactor is designed for long-distance making and breaking of circuit, frequent starting and controlling of AC motors in the power systems, with AC 50Hz-60Hz, rated voltage of 1,140V and rated current to 1000A. It also can be equipped with thermal relay and all kinds of protection apparatus like electromagnetic starter, especially applied to explosion-proof starter and so on. 2. Main technical parameter Rated voltage: 1140 V Control voltage: 36 V, 110 V, 220 V, 380 V Rated current: 1000A Opening distance: 2±0.2 mm Over travel: 1±0.2 mm Final pressure: 30±3 N Main circuit power frequency voltage withstand: 4200 V Auxiliary circuit power frequency voltage withstand: 2500 V Control circuit power frequency voltage withstand: 2000 V Making capacity: 10Ie,100 times Breaking capacity: 8Ie,25 times Limit breaking current(A): 10000,3 times Electricity life times AC3: 60*104 Electricity life times AC4: 1.5*104 Mechanical life times: 300*104 Overload capacity: 8Ie 10S Remark: “Ie” is Rated current of main circuit.
Supplier: Steel scrap, rails for rerolling, shredded 210/211, hms 1 and 2 80/20, hms 1, steel turning, tire wire
Supplier: Japanese quality switchgear components, breakers, magnetic contactors, switches, pilot lights, pushbuttons, panel instrumentations, power management meter, protection relays, transformers, inverters, ups.
Supplier: 1.( origin : russia / kazakhstan ) en590, jet a1, jp54, lng, urea, petroleum coke etcpetroleum coke ( petcoke ), etc 2. sugar icumsa 45 ( origin : brazil ) & non gmo soybean 3. ( origin : south korea ) power cable, control cable, cable & wire, instrument cable, silicon insulated cable, armored cable, thermocouple extension cable, fiber optic communication cable, coxial cable, marine cable, offshore cable
Supplier: Motorcycle helmets, accessories, components miniature circuit breaker, auto transfer switch for generators, pump controllers generators upto 7.0 kva & its parts battery inverters, voltage stabilizers for home & industrial use gulf course maintenance equipment bed sheets and bed covers with pillow covers
SANDI SERIES charging module is for electric vehicle charging station. With single-phase non neutral conductor AC input, it has the advantages of high efficiency, high power density and low harmonic. Functional details 1. Hot plug Plug technology is applied to the charging module to provide convenience for installation and maintenance. The access of the charging module to the system shall not disturb the output voltage of the system. 2. Advanced current sharing technology Under constant voltage working mode, the charging modules can share current automatically within 10S, with degree of unbalance less than �±0.5A. 3. Control of input limited power Refer to Fig. 1-10 for the relation between the output power and input voltage of the charging module. When the input voltage is within 360 Vac ~ 450 Vac (return difference is less than 5V), the module can output the maximum power of 20 KW; when the input voltage is within 260 Vac ~ 320 Vac, the module can still work normally under limited power mode. 4. Control of output constant power When there is a rated input voltage, the output power of the module is 20 KW. Refer to Fig. 11 for the relation between the output voltage and the output current of the module. The SD75050 module uses two operating modes with output voltage ranges of 50 to 750V. The module only selects the operating mode based on the value of the received demand voltage, and does not select the operating mode based on the actual output voltage. 5. Temperature limited power 6. Regulation of output current limiting point 8. Regulation of output voltage The output voltage of the module can be regulated constantly through the external monitoring module, with regulation range of 50Vdc ~ 750Vdc and minimum regulation step of 0.1 Vdc. 9. Fan control The built-in processor of the module can regulate the speed of the fan according to the internal temperature and output current of the module. 10. Protection of input overvoltage/ voltage shortage 11. Output overvoltage protection The overvoltage protection point is 260Vdc ~770Vdc (�±10 Vdc). Default is 778Vdc.The module can be started after manual intervention upon overvoltage protection. 12. Over-temperature protection The environmental over-temperature protection point is 80�°C. When the DC panel has a temperature over 100�°C, the module will stop working; when the DC panel has a temperature below 90�°C, the module will automatically work again. 13. Protection of internal bus fault When the internal bus voltage of the module is beyond the overvoltage/ voltage shortage protection point, the module will be powered off automatically. At this time, there is no output from the module and the fault indicator light is on. 14. Short circuit protection In case of short circuit of the module, it will be subjected to protective shutdown and the red indicator light of the panel is on, and this condition will be transmitted to the monitor of the "module fault".